EN 50288-7 Hypron® XLPE Insulation OS Armoured Fire Retardant

Link senden drucken Ihr Kontakt
EN 50288-7 Hypron® XLPE Insulation OS Armoured Fire Retardant - Instrumentation cables 170/300 V
- Overall Screen (OS)
- Lead free
- Aliphatic and aromatic hydrocarbons resistant
Normen
International  IEC 60332-3-22 Cat.A
Beschreibung

 

Applications

These instrumentation and communication cables are used to transmit analogue or digital signals in measurement and process control in moist areas and where aliphatic and aromatic hydrocarbons may be present. They are well adapted to underground use in industrial applications where chemical and mechanical protections are needed (refinery areas, chemical plant...). Hypron® offers an alternative to conventional lead sheathed cable and is an environmental friendly solution..

 

Design

Conductor:

Stranded bare copper class 2

Insulation:

Cross-linked polyethylene (XLPE)

Binder tape

Bedding

Inner sheath:

Polyvinyl chloride (PVC)

Colour: black

Overall screen/sealing barrier

Tinned copper drain wire 

Aluminium backed polyethylene tape

Bedding:

High density polyethylene (PE)

Colour: black

Special sheath (intermediate sheath):

Polyamide

Armour:

Galvanized steel wires (SWA)

Outer sheath:

Polyvinyl chloride (PVC)

Colour: black

Other colour on request

 

Core identification

Pair: white - black
Quad: white - black - red - blue (2 pair cables assembled as a quad)
White core printed with pair number
 

 

Marking

NEXANS 279 XLPE/PVC/AL/HDPE/NC/SWA/PVC 170/300V Nber of pairs & cross-section Cu IEC 60332-3-22(A) MM YYYY Manufacturing number + metric marking

 

Standards

EN 50288-7 (design guide-lines)



Dokumente zum Thema
  Electrical Charasteristics  (30.7kb)



 TOP
Eigenschaften
Konstruktionsmerkmale
Leitermaterial Kupfer, blank  
Leitertype Stranded, Class 2  
Isolierung VPE (vernetztes Polyethylen)  
Innenmantel PVC  
Gemeinsamer Schirm Tinned copper drain wire + aluminium/polyethylene tape  
Bettungsmaterial High-density polyethylene (PE)  
Zwischenmantel Polyamide  
Armierung verzinkte Stahldraehte  
Außenmantel PVC  
Bleifrei Ja  
Schutz Yes  
Elektrische Eigenschaften
Nennspannung Uo/U 170/300V  
Mechanische Eigenschaften
Mechanische Festigkeit gegen Schläge Gut  
Anwendungsmerkmale
flammwidrig IEC 60332-3-22  
Chemische Beständigkeit Aliphatic and aromatic hydrocarbons resistant  
Elektromagnetisch geschirmt Ja  
Betriebstemperatur -20 .. 60°C  
Max. Betriebstemperatur am Leiter 90°C  
Standard EN  

 TOP
Parametrische Suche
Anzahl Paare  
Leiterquerschnitt  mm²
Ausführen
Zurücksetzen
Ihre Wahl   30/30
Alle Artikel wählen Nexans Ref. Name Anzahl Paare Leiter (mm²)
Make to order product EN 50288-7 Hypron® XLPE OS Armoured 1x2x0,5 1 0,5
Make to order product EN 50288-7 Hypron® XLPE OS Armoured 2x2x0,5 2 0,5
Make to order product 10187666 EN 50288-7 Hypron® XLPE OS Armoured 5x2x0,5 5 0,5
Make to order product 10164894 EN 50288-7 Hypron® XLPE OS Armoured 10x2x0,5 10 0,5
Make to order product EN 50288-7 Hypron® XLPE OS Armoured 20x2x0,5 20 0,5
Make to order product EN 50288-7 Hypron® XLPE OS Armoured 30x2x0,5 30 0,5
Make to order product EN 50288-7 Hypron® XLPE OS Armoured 1x2x0,75 1 0,75
Make to order product EN 50288-7 Hypron® XLPE OS Armoured 2x2x0,75 2 0,75
Make to order product 10187674 EN 50288-7 Hypron® XLPE OS Armoured 5x2x0,75 5 0,75
Make to order product 10187677 EN 50288-7 Hypron® XLPE OS Armoured 10x2x0,75 10 0,75
Make to order product EN 50288-7 Hypron® XLPE OS Armoured 20x2x0,75 20 0,75
Make to order product EN 50288-7 Hypron® XLPE OS Armoured 30x2x0,75 30 0,75
Make to order product EN 50288-7 Hypron® XLPE OS Armoured 1x2x1 1 1
Make to order product EN 50288-7 Hypron® XLPE OS Armoured 2x2x1 2 1
Make to order product 10187683 EN 50288-7 Hypron® XLPE OS Armoured 5x2x1 5 1
Make to order product 10187686 EN 50288-7 Hypron® XLPE OS Armoured 10x2x1 10 1
Make to order product EN 50288-7 Hypron® XLPE OS Armoured 20x2x1 20 1
Make to order product EN 50288-7 Hypron® XLPE OS Armoured 30x2x1 30 1
Make to order product EN 50288-7 Hypron® XLPE OS Armoured 1x2x1,5 1 1,5
Make to order product EN 50288-7 Hypron® XLPE OS Armoured 2x2x1,5 2 1,5
Make to order product 10187691 EN 50288-7 Hypron® XLPE OS Armoured 5x2x1,5 5 1,5
Make to order product 10187694 EN 50288-7 Hypron® XLPE OS Armoured 10x2x1,5 10 1,5
Make to order product EN 50288-7 Hypron® XLPE OS Armoured 20x2x1,5 20 1,5
Make to order product EN 50288-7 Hypron® XLPE OS Armoured 30x2x1,5 30 1,5
Make to order product 10187699 EN 50288-7 Hypron® XLPE OS Armoured 1x2x2,5 1 2,5
Make to order product 10187700 EN 50288-7 Hypron® XLPE OS Armoured 2x2x2,5 2 2,5
Make to order product 10187703 EN 50288-7 Hypron® XLPE OS Armoured 5x2x2,5 5 2,5
Make to order product 10187707 EN 50288-7 Hypron® XLPE OS Armoured 10x2x2,5 10 2,5
Make to order product 10187712 EN 50288-7 Hypron® XLPE OS Armoured 20x2x2,5 20 2,5
Make to order product EN 50288-7 Hypron® XLPE OS Armoured 30x2x2,5 30 2,5
Zu den Favoriten hinzufügen

 TOP
Verkaufs- und Lieferinformationen

Other fire performances IEC 60332-1 or IEC 60332-3-24(C) on request.


Minimum bending radius:

15 x outer diameter
To be doubled during laying operations


Tinned copper conductors available on request

Nexans © copyright 2001 - 2012   Impressum | Kontakt | Inhaltsverzeichnis