Über Nexans
Produkte & Lösungen
Kundenservice
Jobs & Karriere
Nachrichten & Presse
These instrumentation and communication cable are used to transmit analogue or digital signals in measurement and process control where chemicals may be present. The individual screening of each pair limits the consequence of crosstalk. They maintain circuit integrity when exposed to fire.
Conductor:
Stranded bare copper class 2
Insulation:
Silicone rubber (Sil)
Individual screen:
Polyester tape
Tinned copper drain wire
Aluminium backed polyester tape
Overall screen:
Copper backed polyester tape
Outer sheath:
Polyvinyl chloride (PVC)
Colour: black
Other colour on request.
Pair: white - black White core printed with pair number
NEXANS 279 SIL/IND.+OA.SCR/PVC 170/300V Nber of pairs & cross-section Cu IEC 60331 IEC 60332-3-22(A) MM YYYY Manufacturing number + metric marking
EN 50288-7 (Design guide-lines)
Minimum bending radius:
10 x outer diameter To be doubled during laying operations
Tinned copper conductors available on request