EN 50288-7 XLPE Insulation IOS Armoured Fire Retardant

Link senden drucken Ihr Kontakt
EN 50288-7 XLPE Insulation IOS Armoured Fire Retardant - Instrumentation cables 170/300 V
- Individual & Overall Screen (IOS)
- Oil resistant
Normen
International  IEC 60332-3-22 Cat.A
Beschreibung

Applications

These Instrumentation and communication are used to transmit analogue or digital signals in measurement and process control. They are well adapted to underground use in industrial applications where chemical and mechanical protections are needed (refinery areas, chemical plant...). The individual screening of each pair limits the consequence of crosstalk.

 

Design

Conductor:

Stranded bare copper class 2

Insulation:

Cross-linked polyethylene (XLPE)

Individual screen

Polyester tape

Tinned copper drain wire 

Aluminium backed polyester tape

Polyester tape

Overall screen

Polyester tape

Tinned copper drain wire 

Aluminium backed polyester tape

Inner sheath:

Polyvinyl chloride (PVC)

Armour:

Galvanized steel wires (SWA)

Outer sheath:

Polyvinyl chloride (PVC) 

Colour: black 

Other colour on request

 

Core identification

Pair: white - black
White core printed with pair number

 

Marking

NEXANS 279 XLPE/IND.+OA.SCR/PVC/SWA/PVC 170/300V Nber of pairs & cross-section Cu IEC 60332-3-22(A) MM YYYY Manufacturing number + metric marking

 

Standards

EN 50288-7 (design guide-lines)


 TOP
Eigenschaften
Konstruktionsmerkmale
Leitermaterial Kupfer, blank  
Leitertype Stranded, Class 2  
Isolierung VPE (vernetztes Polyethylen)  
Einzeln geschirmt Tinned copper drain wire + aluminium/polyester tape  
Gemeinsamer Schirm Tinned copper drain wire + aluminium/polyester tape  
Innenmantel PVC  
Armierung verzinkte Stahldraehte  
Außenmantel PVC  
Schutz Yes  
Elektrische Eigenschaften
Nennspannung Uo/U 170/300V  
Mechanische Eigenschaften
Mechanische Festigkeit gegen Schläge Gut  
Anwendungsmerkmale
flammwidrig IEC 60332-3-22  
Ölbeständigkeit Ja  
Elektromagnetisch geschirmt Ja  
Betriebstemperatur -20 .. 60°C  
Max. Betriebstemperatur am Leiter 90°C  
Standard EN  

 TOP
Parametrische Suche
Anzahl Paare  
Leiterquerschnitt  mm²
Ausführen
Zurücksetzen
Ihre Wahl   25/25
Alle Artikel wählen Nexans Ref. Name Anzahl Paare Leiter (mm²)
Make to order product 10134811 EN 50288-7 XLPE IOS Armoured 2x2x0,5 2 0,5
Make to order product 10134818 EN 50288-7 XLPE IOS Armoured 2x2x0,75 2 0,75
Make to order product 10134825 EN 50288-7 XLPE IOS Armoured 2x2x1 2 1
Make to order product 10134832 EN 50288-7 XLPE IOS Armoured 2x2x1,5 2 1,5
Make to order product 10168655 EN 50288-7 XLPE IOS Armoured 2x2x2,5 2 2,5
Make to order product 10168665 EN 50288-7 XLPE IOS Armoured 5x2x0,5 5 0,5
Make to order product 10168748 EN 50288-7 XLPE IOS Armoured 5x2x0,75 5 0,75
Make to order product 10168654 EN 50288-7 XLPE IOS Armoured 5x2x1 5 1
Make to order product 10168756 EN 50288-7 XLPE IOS Armoured 5x2x1,5 5 1,5
Make to order product 10168697 EN 50288-7 XLPE IOS Armoured 5x2x2,5 5 2,5
Make to order product 10168644 EN 50288-7 XLPE IOS Armoured 10x2x0,5 10 0,5
Make to order product 10168724 EN 50288-7 XLPE IOS Armoured 10x2x0,75 10 0,75
Make to order product 10168681 EN 50288-7 XLPE IOS Armoured 10x2x1 10 1
Make to order product 10168758 EN 50288-7 XLPE IOS Armoured 10x2x1,5 10 1,5
Make to order product 10168631 EN 50288-7 XLPE IOS Armoured 10x2x2,5 10 2,5
Make to order product 10134816 EN 50288-7 XLPE IOS Armoured 20x2x0,5 20 0,5
Make to order product 10134823 EN 50288-7 XLPE IOS Armoured 20x2x0,75 20 0,75
Make to order product 10134830 EN 50288-7 XLPE IOS Armoured 20x2x1 20 1
Make to order product 10134837 EN 50288-7 XLPE IOS Armoured 20x2x1,5 20 1,5
Make to order product 10168683 EN 50288-7 XLPE IOS Armoured 20x2x2,5 20 2,5
Make to order product EN 50288-7 XLPE IOS Armoured 30x2x0,5 30 0,5
Make to order product EN 50288-7 XLPE IOS Armoured 30x2x0,75 30 0,75
Make to order product EN 50288-7 XLPE IOS Armoured 30x2x1 30 1
Make to order product EN 50288-7 XLPE IOS Armoured 30x2x1,5 30 1,5
Make to order product EN 50288-7 XLPE IOS Armoured 30x2x2,5 30 2,5
Zu den Favoriten hinzufügen

 TOP
Verkaufs- und Lieferinformationen

Other fire performances IEC 60332-1 or IEC 60332-3-24(C) and enhanced hydrocarbon resistance on request.


Minimum bending radius:

10 x outer diameter
To be doubled during laying operations


Tinned copper conductors available on request


Zusatzinformation
EN 50288-7 XLPE Insulation IOS Armoured Fire Retardant   Electrical Characteristics (30 kB)