U-1000 AR2V (industrial rigid unarmoured)

Link senden drucken Ihr Kontakt
U-1000 AR2V (industrial rigid unarmoured) Low voltage power cable for fixed application,
Aluminium conductor, XLPE insulation and PVC outer sheath.
Normen
National  NF C 32-321
Beschreibung

Application

U-1000 AR2V aluminium cables can be used in all low voltage power installations.
This product is used in photovoltaic applications (branded KEYLIOS®)

 

Installation

These cables can be fixed on cable trays, within conduits or fixed to walls.
They also can be buried directly with extra mechanical protection.

 

Design

  • Conductor: stranded circular aluminium - class 2 according to NFC 32-013 / IEC 60228 / HD 383
  • Insulation: XLPE - cores identification by colours
  • Laying up (for multi conductors): with non hygroscopic filler
  • Outer sheath : Lead free black PVC 

Construction according to AD8 is possible on request

  

Marking

N (x ou G) S mm² U-1000 AR2V NF - USE N° Usine S.Y + Sans Pb

  • N = number of cores
  • S = section in mm²
  • G = with Green-Yellow
  • x = without Green-Yellow

 TOP
Eigenschaften
Konstruktionsmerkmale
Leitermaterial Aluminium/polyester tape  
Leiterflexibilität KL.2=mehrdrähtig  
Isolierung VPE  
Außenmantel PVC  
Mantelfarbe Schwarz  
Bleifrei Ja  
Elektrische Eigenschaften
Nennspannung Uo/U 0.6/1 kV  
Mechanische Eigenschaften
Mechanische Festigkeit gegen Schläge Gut  
Anwendungsmerkmale
Max. Betriebstemperatur am Leiter 90°C  
Max. Kurzschlusstemperatur am Leiter 250°C  
Betriebstemperatur -25 .. 60°C  
Witterungsbeständig Sehr gut  
Flammwidrig C2, NF C 32-070  
Chemische Beständigkeit zufällig  
Wasserdicht Very good  

 TOP
New cores identification
Core identification in accordance with HD 308 S2 (October 2001)Identification of cores in cables and flexible cords.

 

Number of cores

HD 308 S2 since january 2004

G (earth core)

X (without earth core)

1

Black (preferential)

Black (preferential)

2

Blue + Brown

Blue + Brown

3*

Green - Yellow + Blue + Brown 

Brown + Black + Grey

3**

 

Blue + Brown + Black

4

Green - Yellow + Brown + Black + Grey

Blue + Brown + Black + Grey

5

Green - Yellow + Blue + Brown + Black + Grey

Blue + Brown + Black + Grey + Black

>  5

White printed numbers + 1 Green - Yellow

White printed numbers

* For the cables without Green/Yellow with a cross-section >4mm²

** For the cables without Green/Yellow with a cross-section of 1,5mm² & 2,5mm²


 TOP
Laying conditions

Without mechanical protection, those cables can be fixed on the wall, cables trays or cable laders.

In buildings with explosion risks, they will be installed with particular protection. In this case, step down of 15% current carrying capacities.

 

Pulling on cable conductors

Tensile stress per mm2 of section shall in no case exceed 5 daN for LV aluminium cable.

The maximum pulling load must never exceed 2000 daN even rule above-mentionned sometimes leads to higher values for large section of cable.