Temporary site cable 2XS2Y RM 64/110 (123) kV

Send link to this page print Your Nexans contact on this page
Temporary site cable 2XS2Y RM 64/110 (123) kV International Designation  64/110 (123)kV Copper XLPE Cable
Single core XLPE insulated cable for temporary use
Standards
National  Factory standard
Description

Stranded copper conductor class 2 according to IEC 60228, semi conducting conductor screen, insulation of cross-linked polyethylene (XLPE), semi conducting insulation screen, semi conducting bedding, copper screen, bedding, PE sheath.

Temporary construction cables are used for maintance, repair and modification of overhead lines and electric power transformation substations. The cables act as a temporary bridging or apportionment of cable routes as well as emergency power supply. By using pre-assembled flexible outdoor terminations and special drums a fast and easy application on the construction site is reached. Usual single lenghts are 50 - 400 m.

All Nexans temporary site cables can be partial discharge tested after using.   

All high voltage cables are manufactured on the basis of specifications and can be adapted to the requirements of the customer. Therefore, all technical information are purely for information purposes and the electrical characteristics are calculated for values which are specified in the data sheets and a cable axis-center distance of 0,15 m and solar radiation. For your specific requirements and laying arrangements please don't hesitate to contact us.


 TOP
Characteristics
Construction characteristics
Conductor material Aluminium / Polyester tape  
Insulating material XLPE  
Screen Copper wire  
Outer sheath Tinned copper drain wire + aluminium/polyester tape  
Lead free Yes  
Halogen free PE  
Electrical characteristics
Frequence 50Hz  
Operating voltage 110kV  
Maximum operating voltage 123kV  
Usage characteristics
Minimum installation temperature -20°C  
Bending factor when installed 15(xD)  
Bending factor when laying 30(xD)  
Max. conductor temperature in service 90°C  

 TOP
Your selection
Conductor cross-section  mm²
Nominal insulation thickness  mm
Screen section  mm²
Nominal outer sheath thickness  mm
Outer Diameter  mm
Approximate weight  kg/m
Permissible current rating in open air  A
Permissible transmission capacity, air  MVA
Apply
Reset
Results   3/3
Select all Items Nexans ref. Cross section (mm²) Nom. insulation thick. (mm) Screen section (mm²) Nom. outer sheath thick. (mm) Outer Diameter (mm) Approx. weight (kg/m) Perm. current rating open air (A) Transm. capacity, air (MVA)
Make to order product 14313511 150 15.0 35 3.7 58.5 3.9 475 90
Make to order product 14317311 300 13.0 35 3.7 59 5.2 692 132
Make to order product 14315611 630 18.0 35 4.0 82 10.2 1084 206