NYFGY 3,6/6 kV, acc. to DIN VDE 0271

Description
Three-core PVC-insulated copper cables with galvanized flat steel wire armouring
Description
Standards
National : DIN VDE 0271Description
Application
Installation in ground, outdoors, in water, indoors and in cable ducts if greater mechanical protection is required or if greater tensile stresses are to be expected during installation and operation.
Construction
Conductor: stranded copper wires
Insulation: PVC (polyvinyl chloride)
Inner covering: extruded or lapped
Armour: galvanized flat steel wires and counter helix of galvanized steel tape
Outer sheath: PVC (polyvinyl chloride); Colour: red
Characteristics
Construction characteristics | |
---|---|
Lead free | Yes |
Dimensional characteristics | |
Nominal insulation thickness | 3.4mm |
Armour thickness | 0.8mm |
Electrical characteristics | |
Test voltage | 11kV |
Maximum operating voltage | 7.2kV |
Rated Voltage Uo/U (Um) | 3.6/6 kV |
Usage characteristics | |
Ambient installation temperature, range | -5 .. 50°C |
Bending factor when laying | 15(xD) |
Operating temperature, range | -30 .. 70°C |
Specific characteristics | |