AFNOR NF M 87-201 OS Armoured (EGFA)

Description
- Thermocouple cables 250 V
- Overall Screen (OS)
- Hydrocarbons resistant
Description
- Overall Screen (OS)
- Hydrocarbons resistant
Standards
International : IEC 60332-1-2; IEC 60584-3National : NF C 32-070/C2; NF C 42-324
Description
Applications
These compensation and extension cables are used with thermocouples for temperature measurements. They are well adapted to underground use in industrial applications where hydrocarbons may be present and mechanical protections are needed (rafinery areas, chemical plant...)
Design
Conductor:
Metal in accordance with the thermocouple,
- for single pair cables solid cross-section 1.34 mm² (1 x 1.30 mm) or stranded cross-section 1 mm² (14 x 0.30 mm)
- multipair cables : solid cross-section 0.5 mm² (1 x 0.8 mm)
Insulation:
Polyvinyl chloride (PVC)
Collective screen:
Polyester tape
Tinned copper drain wire
Aluminium/polyester tape
Inner sheath:
Polyvinyl chloride (PVC)
Armour:
Paraffin-waxed crepe paper
Double steel tape
Outer sheath:
Polyvinyl chloride (PVC)
Colour: depends on thermocouple type
Core identification
See "Identification sheet"
Standards
NF M 87201
Marking
For type JC - TC - EC - KC - BC: type - (Class) - Nber of pair and cross-section - NEXANS 279 + metric marking
For type KCA - KCB - NC - SCA - SCB - RCA - RCB (IEC 60584-3) IEC - type - (Class) - Nber of pair and cross-section - NEXANS 279 + metric marking
Characteristics
Construction characteristics | |
---|---|
Insulation | PVC |
Overall screen | Tinned copper drain wire + aluminium/polyester tape |
Inner sheath | PVC |
Armour type | Two steel tapes |
Outer sheath | PVC |
Protection | Yes |
Electrical characteristics | |
Operating voltage | 250V |
Mechanical characteristics | |
Mechanical resistance to impacts | Good |
Usage characteristics | |
Flame retardant | NFC 32070 C2, IEC 60332-1-2 |
Chemical resistance | Hydrocarbons resistant |
Electro magnetic interference resistance | Yes |
Operating temperature, range | -20 .. 60°C |
Max. conductor temperature in service | 70°C |
Standard | NFM |
Specific characteristics | |
See all products | |
|
Products and services
Docs and info
* Thermocouple type
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TC – Copper/copper nickel for copper/copper nickel thermocouple |
|
|
|
|
|
|
|
JC – Iron/copper nickel for iron/copper nickel thermocouple |
|
|
|
|
|
|
|
EC – Nickel chromium/copper nickel for nickel chromium/copper nickel thermocouple |
|
|
|
|
|
|
|
KC – Nickel chromium/nickel aluminium for nickel chromium/nickel aluminium thermocouple |
|
|
|
|
|
|
|
KCA – Iron/copper nickel for nickel chromium/nickel aluminium thermocouple |
|
|
|
|
|
|
|
KCB – Copper/copper nickel for nickel chromium/nickel aluminium thermocouple |
|
|
|
|
|
|
|
NC – Nickel chromium silicium/nickel silicium for nickel chromium silicium/nickel silicium thermocouple |
|
|
|
|
|
|
|
SC RC – Copper/copper nickel for platinium rhodium thermocouple |
|
|
|
|
|
|
|
BC – Copper/copper alloy for platinium rhodium/platinium rhodium thermocouple |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Selling information
Minimum bending radius:
10 x outer diameter
To be doubled during laying operations