AFNOR NF M 87-202 IOS Unarmoured

Description
- Instrumentation cables 250 V
- Individual & Overall Screen (IOS)
- Hydrocarbons resistant
Description
- Individual & Overall Screen (IOS)
- Hydrocarbons resistant
Standards
International : IEC 60332-1-2National : NF C 32-070/C2
Description
Applications
These instrumentation and communication cable are used to transmit analogue or digital signals in measurement and process control where hydrocarbons may be present. The individual screening of each pair limits the consequence of crosstalk.
Nexans code
- 1st serie = number of pairs, triples or quads: 01 to 27
- 2nd serie = pair (IP), triple (IT), quad (IQ)
- 3rd serie = conductor 05 (1 x 0.8 mm), 09 (7 x 0.4 mm) or 15 (7 x 0.52 mm)
- 4th serie = collective screen (EG), individual screen + collective screen (EI)
- 5th serie = mechanical protection: without metal tape (SF), with steel tape (FA), with lead and steel tape (PF)
Design
Conductor:
- Solid plain copper 0.50 mm² (1 x 0.80 mm) or stranded plain copper cross-section 0.88 mm² (7 x 0.40 mm)
Insulation:
- Polyvinyl chloride (PVC)
Individual screen:
- Polyester tape
- Tinned copper drain wire
- Aluminium/polyester tape
Individual sheath:
- Polyvinyl chloride (PVC)
Collective screen:
- Polyester tape
- Tinned copper drain wire
- Aluminium/polyester tape
Outer sheath:
- Polyvinyl chloride (PVC)
- Colour: light-blue or grey
Core identification
Pair: natural - red
Triple: natural - red - blue
Blue individual sheath printed with pair or triple number
Marking
NEXANS 279 - Number of pair/triple IP/IT 05/09 EI SF + metric marking
Characteristics
Construction characteristics | |
---|---|
Conductor material | Plain copper |
Insulation | PVC |
Individual screen | Tinned copper drain wire + aluminium/polyester tape |
Individual sheath | PVC |
Overall screen | Tinned copper drain wire + aluminium/polyester tape |
Outer sheath | PVC |
Sheath colour | Light blue |
Electrical characteristics | |
Operating voltage | 250V |
Usage characteristics | |
Flame retardant | NFC 32070 C2, IEC 60332-1-2 |
Chemical resistance | Hydrocarbons resistant |
Electro magnetic interference resistance | Yes |
Operating temperature, range | -20 .. 60°C |
Max. conductor temperature in service | 70°C |
Standard | NFM |
Specific characteristics | |
See all products | |
|
Products and services
Docs and info
Selling information
Minimum bending radius:
1 core: 10 x outer diameter
To be doubled during laying operations