AFNOR NF M 87-202 OS Armoured

Description
- Instrumentation cables 250 V
- Overall Screen (OS)
- Hydrocarbons resistant
Description
- Overall Screen (OS)
- Hydrocarbons resistant
Standards
International : IEC 60332-1-2National : NF C 32-070/C2
Description
Applications
These instrumentation and communication cable are used to transmit analogue or digital signals in measurement and process control.They are well adapted to underground use in industrial application where chemical and mechanical protections are needed (refinery areas, chemical plant…) .
Nexans code
1st serie = number of pairs, triples or quads: 01 to 27
- 2nd serie = pair (IP), triple (IT), quad (IQ)
- 3rd serie = conductor 05 (1 x 0.80 mm), 09 (7 x 0.40 mm) or 15 (7 x 0.52 mm)
- 4th serie = overall screen (EG), individual screen + overall screen (EI)
- 5th serie = mechanical protection: without metal tape (SF), with steel tape (FA), with lead and steel tape (PF)
Design
Conductor:
- Solid plain copper 0.50 mm² (1 x 0.80 mm) or stranded plain copper cross-section 0.88 mm² (7 x 0.40 mm) or 1.5 mm² (7 x 0.52 mm)
Insulation:
- Polyvinyl chloride (PVC)
Overall screen:
- Polyester tape
- Tinned copper drain wire
- Aluminium/polyester tape
Inner sheath:
- Polyvinyl chloride (PVC)
Armour:
- Double steel tape
Outer sheath:
- Polyvinyl chloride (PVC)
- Colour: light-blue or grey
Core identification
Pair: natural - red
Triple: natural - red - blue
Quad: natural - red - blue - yellow
Natural cores printed with pair/triple number
Marking
NEXANS 279 - Number of pairs/triples/quads IP/IT/IQ 05/09/15 EG FA + metric marking
Characteristics
Construction characteristics | |
---|---|
Conductor material | Plain copper |
Insulation | PVC |
Overall screen | Tinned copper drain wire + aluminium/polyester tape |
Inner sheath | PVC |
Armour type | Steel tapes |
Outer sheath | PVC |
Electrical characteristics | |
Operating voltage | 250V |
Mechanical characteristics | |
Mechanical resistance to impacts | Good |
Usage characteristics | |
Flame retardant | NFC 32070 C2, IEC 60332-1-2 |
Chemical resistance | Hydrocarbons resistant |
Electro magnetic interference resistance | Yes |
Operating temperature, range | -20 .. 60°C |
Max. conductor temperature in service | 70°C |
Standard | NFM |
Specific characteristics | |
See all products | |
|
Products and services
Docs and info
Selling information
Minimum bending radius:
10 x outer diameter
To be doubled during laying operations