IEC 60502-1 Hypron® Unarmoured Fire retardant

Description
- 0.6/1 kV Power and control cables
- Lead free
- Aliphatic and aromatic hydrocarbons resistant
Description
- Lead free
- Aliphatic and aromatic hydrocarbons resistant
Standards
International : IEC 60228; IEC 60332-3-22Description
Applications
These power and control cables are used for electricity supply in low voltage installation system, in moist areas and where hydrocarbons may be present. Hypron® offers an alternative to conventional lead covered cable and is an environmental friendly solution.
Design
Conductor:
Solid plain copper: 1.5 to 4 mm²
Stranded plain copper: 1.5 to 630 mm²
Insulation:
Cross-linked polyethylene (XLPE)
Bedding (optional):
Inner sheath acting as a filler with practically zero thickness or assembling polyester tape
Inner covering (optional): inner sheath
Polyvinyl chloride (PVC) Colour black
Screen/sealing barrier:
Tinned copper drain wire, Aluminium/polyethylene tape
Sheath:
High density polyethylene (PE) Colour: black
Special sheath (intermediate sheath):
Polyamide
Outer sheath:
Polyvinyl chloride (PVC) Colour: black. Other colour on request
Core identification
1 core: black
2x to 5G cores: according to HD 308 S2
Above 5 cores: black core printed with white number
Marking
NEXANS 279 XLPE/AL/HDPE/NC/PVC 0.6/1 kV Nber of cores and cross section Cu IEC 60332-3-22(A) MM YYYY Manufacturing number + meter marking.
IEC 60502-1 (design guide-lines),
Characteristics
Construction characteristics | |
---|---|
Conductor material | Plain copper |
Insulation | XLPE (Cross-linked Polyethylene) |
Inner sheath | PVC |
Intermediate sheath | Polyamide |
Outer sheath | PVC |
Protection | no |
Lead free | Yes |
Electrical characteristics | |
Rated Voltage Uo/U (Um) | 0.6/1 kV |
Usage characteristics | |
Fire retardant | IEC 60332-3-22 |
Chemical resistance | Aliphatic and aromatic hydrocarbons resistant |
Max. conductor temperature in service | 90°C |
Operating temperature, range | -20 .. 60°C |
Specific characteristics | |
See all products | |
|
Products and services
Docs and info
Related documents
Selling information
Other fire performances IEC 60332-1 or IEC 60332-3-24(C) on request.
Minimum bending radius:
1 core: 15 x outer diameter
Multicores: 17 x outer diameter
To be doubled during laying operations
Cables with reduced neutral and larger cross-section on request