Description
Standards
International : EN 50575; EN 60228National : NF F 55-625
Description
Application
These cables are used for fixed power or lighting installations (1000 V) and fixed traction circuits (1800 V) in tunnels and underground stations.
Fire resistance
- Flame retardant: According to RATP K20 specification
- Fire retardant: According to RATP K20 specification
- Low smoke: According to RATP K20 specification
- Without Halogen: According to RATP K20 specification
- Low Toxicity : According to RATP K20 specification
- Low corrosivity: According to RATP K20 specification
Design
- Conductor: Bare copper class 1 or 2
- Insulation: Cross-linked polyethylene (XLPE)
- Outer sheath: Polyolefine without halogen
Colour : black or yellow/green (Y/G)
Marking
1000 V cables: 1000 - Nber of cores & cross-section - SH -NF F 55-625 - NEXANS 279 - WW - YY - B2ca-s1a, d0, a1 - Manufacturing n° - DoP:1000292-FRME + metric marking
1800 V cables: 1800 - Nber of cores & cross-section - SH -NF F 55-625 - NEXANS 279 - WW - YY - B2ca-s1a, d0, a1 - Manufacturing n° - DoP:1000292-FRME + metric marking
Core identification
According to NF F 55625
1x: black
Reaction to fire: B2ca-s1a, d0, a1
Characteristics
Construction characteristics | |
---|---|
Conductor material | Plain copper |
Insulation | XLPE (Cross-linked Polyethylene) |
Outer sheath | Halogen free polyolefin |
Halogen free | IEC 60754-1 & EN 60754-1 |
Usage characteristics | |
Flame retardant | IEC 60332-1-2 & EN 60332-1-2 |
Smoke density | IEC 61034-2 & EN 61034-2 |
Gases toxicity | Low |
Gases corrosivity | IEC 60754-2 & EN 60754-2 |
Max. conductor temperature in service | 90°C |
Operating temperature, range | -20 .. 60°C |
Specific characteristics | |
See all products | |
|
Products and services
Docs and info
-
COMPLEMENT
Bending Radius
r = 6 x maximum outer diameter
Declaration of Performance
Declaration of Performance No: 1000292-FRME
- Certification Date: 05/09/2017
- AVCP (Assessment and Verification of Constancy of Performance): System 1+
- Notified body : 0081
- Declared performance: Reaction to fire B2ca -s1a,d0,a1 according to EN50575:2014+A1:2016
Nexans ref. | Country ref. | Product Name |
10050523 | NF F 55-625 (K25) 1000V 1x70 G/Y B2ca-s1a, d0, a1 | |
10060688 | NF F 55-625 (K25) 1000V 1x240 B2ca-s1a, d0, a1 | |
10061867 | NF F 55-625 (K25) 1000V 1x120 B2ca-s1a, d0, a1 | |
10080071 | NF F 55-625 (K25) 1000V 1x185 B2ca-s1a, d0, a1 | |
10107732 | NF F 55-625 (K25) 1000V 1x50 B2ca-s1a, d0, a1 | |
10108769 | NF F 55-625 (K25) 1000V 1x10 B2ca-s1a, d0, a1 | |
10191303 | NF F 55-625 (K25) 1000V 1x35 B2ca-s1a, d0, a1 | |
10191304 | NF F 55-625 (K25) 1000V 1x95 B2ca-s1a, d0, a1 | |
10196914 | NF F 55-625 (K25) 1000V 1x6 B2ca-s1a, d0, a1 | |
10270815 | NF F 55-625 (K25) 1000V 1x6 Y/G B2ca-s1a, d0, a1 | |
10270824 | NF F 55-625 (K25) 1000V 1x150 B2ca-s1a, d0, a1 |
Declaration of Performance No: 1000292-FRME
- Certification Date: 09/07/2018
- AVCP (Assessment and Verification of Constancy of Performance): System 1+
- Notified body : 0081
- Declared performance: Reaction to fire B2ca -s1a,d0,a1 according to EN50575:2014+A1:2016
Nexans ref. | Country ref. | Product Name |
10050522 | NF F 55-625 (K25) 1000V 1x25 B2ca-s1a, d0, a1 |