Description
Standards
International : IEC 60228National : DIN VDE 0207 part 20; DIN VDE 0250 part 1; DIN VDE 0250 part 813
Description
Application
Medium-voltage cable WINDLINK® MV-AL (N)TMCGCHXOE in one sheath design was developed for special application conditions in wind turbines. These cables are for fixed installation.
Design
Conductor
Aluminium, flexible stranded, class 2 acc. to DIN EN / IEC 60228
Insulation
- inner semi-conductive stress control layer
- elastomeric rubber compound RHEYCLEAN HV-EPR, quality better than 3GI3 acc. to DIN VDE 0207 part 20, based on EPDM, optimized wall thickness
- outer semi-conductive insulation shield layer, easy strip (thermo strip), compound based on EVA.
All three layers are extruded in one process and free of hollow space.
Screen
Tinned copper wire serving, design acc. to DIN VDE 0250 part 1
Outer sheath
Halogen free, extruded rubber compound, colour: black
Marking
Inkjet-marking (WS), e.g.:
WINDLINK® MV-AL (N)TMCGCHXOE 1x120/16 20/35 kV I NEXANS I week/year
Resistance to:
- oil
- flame-retardant
- temporary influence of seawater
- weather
- ozone influence
Characteristics
Construction characteristics | |
---|---|
Conductor material | Aluminum |
Insulation | RHEYCLEAN-HEPR |
Outer sheath | Halogen free flame retardant |
Sheath colour | Black |
Halogen free | IEC 60754-2 |
Usage characteristics | |
Flame retardant | EN 60332-1-2 |
RoHS compliant | Yes |
Silicone free | Yes |
Limit surface temperature fixed installed | -40 .. 90°C |
Limit surface temperature, flexible application | -25 .. 90°C |
Weather resistance | Yes |
Specific characteristics | |
See all products | |
|