SVMS/SVMS-P Heat-shrinkable in-line joint

Description
Heat-shrinkable in-line joint including mechanical connectors, without/with parking position, suitable for installation under voltage, design acc. to DIN V 47640
Description
Standards
International : HD 631.2 S1 ; IEC 61238-1National : DIN V 47640
Description
Application
SVMS / SVMS-P joints are designed for all 3 1/2, 4 and 5 core polymeric insulated cables (e.g. N(A)YY, N(A)YC(W)Y) with PVC or XLPE insulation as well as for PVC or PE outer sheaths.
The joints are designed for use of mechanical connectors accommodating copper or aluminum conductors. Joints offer a sealed indoor or outdoor application, fully submersible or directly buried.
Technical characteristics
For application SVMS-P including a parking position on conductors for mechanical contacts a connector without oil stop is mandatory. Tube lenghts for inner joints are than different to SVMS once.
Specifications and standards
Heat-shrinkable tubes meet the requirements of CENELEC HD 631.2 S1. The dimensions of the mechanical connectors, that have been tested according to IEC 61238-1 or VDE 0220 part 100 respectively, correspond to DIN V 47640.
Docs and info
-
Design
The joints consist of up to 5 inner and 1 outer heat-shrinkable tube. All tubing in the kit is thick-walled and co-extruded with adhesive quality. Tubes dimensions are according to DIN V 47640.
-
Kit contents
The heat-shrinkable in-line joint kit comprises the following components:
4 (5) x inner joints
1 x overall protection tube
4 (5) x mechanical connectors with/without oil stop
installation instructions -
Ordering instructions
Select the order part number of the joint type according to the cable type and the conductor cross-section:
SVMS HEAT-SHRINKABLE IN-LINE JOINT incl. mechanical connectors with oil stop up to 0.6/1 (1.2) kV without parking position for the connector on the conductors
SVMS-P HEAT-SHRINKABLE IN-LINE JOINT incl. mechanical connectors without oil stop up to 0.6/1 (1.2) kV with parking position for the connector on the conductors
Order example
Heat-shrinkable in-line joint for a 4 core polymeric insulated cable, nominal voltage 0.6/1 kV, conductor cross-section 35-150 mm²
Order part number: 53186 -
Pictograms
-
Technical instructions and application information (accessories)
The data given were determined diligently, but do not release our customers of the duty to carry out tests themselves in order to check the suitability of the products delivered by us for the intended use. We reserve the right to modify characteristic and performance data according to the present state of technology. Processing and use of the products cannot be controlled by us and are therefore exclusively in your field of responsibility.
Our products meet the VDE standards respectively correspond to DIN pages and IEC recommendations.
Attention: Before first design in please contact manufacturer.
The products, described in this catalogue, are designed for connection of bare energy cable conductors (Class 1 & 2) with description of round solid (RE), round stranded (RM), as well as sector solid (SE), sector stranded (SM) and round stranded compacted (RMV) for conductor temperatures up to 90 °C. All conductor filling materials like tapes, yarn, powder or similar need to be completely removed before the installation. A check on basis of the actual existing conductor dimensions by the user is indispensable. This applies also for the application of Class 6 conductors or other special conductor types.
Impact wrenches have to be approved by Nexans! Depending on different conductor material or conductor type, indicated values may differ from test values acc. to IEC 61238-1. The use of fine stranded conductors has to be approved by Nexans Power Accessories Germany GmbH.
Our responsibilities are only those listed in the latest edition of “General terms and conditions for the supply of products and services of the electrical and electronics industry”. We can provide a copy on request.
Our products are mainly delivered in cartons. We only use package materials able to be recycled due to the latest packing system. Collapsible cardboard boxes are not taken back. Please try to order complete standard packages.
Reprinting, even partial, only with special allowance. We reserve the right to alter or modify the characteristics described. Illustrations and drawings may only show a close reflection and are not decisive. The weights are approximate and include the carton package. This catalogue substitutes all former editions. Types or versions not part of the catalogue are available on request.
Hof, January 2020