Description
- Overall Screen (OS)
- Hydrocarbons resistant
Standards
International : IEC 60332-1-2National : NF C 32-070/C2
Description
Applications
These instrumentation and communication cables are used to transmit analogue or digital signals in measurement and process control where hydrocarbons may be present.
Nexans code
- 1st serie = number of pairs, triples or quads: 01 to 27
- 2nd serie = pair (IP), triple (IT), quad (IQ)
- 3rd serie = conductor 05 (1 x 0.8 mm), 09 (7 x 0.4 mm) or 15 (7 x 0.52 mm)
- 4th serie = overall screen (EG), individual screen + overall screen (EI)
- 5th serie = mechanical protection: without metal tape (SF), with steel tape (FA), with lead and steel tape (PF)
Design
Conductor:
- Solid plain copper 0.50 mm² (1 x 0.80 mm) or stranded plain copper cross-section 0.88 mm² (7 x 0.40 mm) or 1.5 mm² (7 x 0.52 mm)
Insulation:
- Polyvinyl chloride (PVC)
Overall screen:
- Polyester tape
- Tinned copper drain wire
- Aluminium/polyester tape
Outer sheath:
- Polyvinyl chloride (PVC)
- Colour: light-blue or grey
Core identification
Pair: natural - red
Triple: natural - red - blue
Quad: natural - red - blue - yellow
Natural cores printed with pair/triple number
Marking
NEXANS 279 - Number of pair/triple/quad IP/IT/IQ 05/09/15 EG SF + metric marking
Characteristics
Construction characteristics | |
---|---|
Conductor material | Plain copper |
Insulation | PVC |
Overall screen | Tinned copper drain wire + aluminium/polyester tape |
Outer sheath | PVC |
Sheath colour | Light blue |
Dimensional characteristics | |
Conductor cross-section | 0.88mm² |
Number of pairs | 0 |
Number of triples | 12 |
Number of quads | 0 |
Minimum outer diameter | 20.7mm |
Maximum outer diameter | 22.9mm |
Approximate weight | 662kg/km |
Electrical characteristics | |
Operating voltage | 250V |
Usage characteristics | |
Flame retardant | NFC 32070 C2, IEC 60332-1-2 |
Chemical resistance | Hydrocarbons resistant |
Electro magnetic interference resistance | Yes |
Operating temperature, range | -20 .. 60°C |
Max. conductor temperature in service | 70°C |
Standard | NFM |
Docs and info
Selling information
Minimum bending radius:
10 x outer diameter
To be doubled during laying operations