Description
Standards
International : IEC 60092-353National : DIN VDE 0250
Description
Approval certificates
Adapted to VDE 250
Application
Especially for frequency converter controlled AC drives. For fixed installation and occasional free flexing indoors in dry, damp and wet conditiones, as well as outdoors for low mechanical stress. Not suitable for the installation direct in ground and in water. Cores are normally identified by colours according to HD 308 S2. This product is also part of our Windlink® offer dedicated to wind turbines.
Design
-
Conductor
plain finely stranded copper, Class 5 according to VDE 0295 or IEC 60228 -
Protective Conductor
plain finely stranded copper, Class 5 according to VDE 0295 or IEC 60228 - for cross sections > 16mm² the protective conductor is divided into 3 cores -
Insulation
halogen free special XLPE according to IEC 60502-4 max. core temperature: 90C° -
Screen
Multilayer screen, EMC - optimized regarding to radio frequency interference field strength and voltage according to EN 55011 or DIN VDE 0875
1. Layer: Al - coated tape
2. Layer: braid of tinned copper wires
-
Outer Sheath
Halogen free compound complying with SHF1 according to IEC 60092-359 and HM4 according to VDE 207 part 24
-
Core identification
Colour: according to HD 308 S2
grey + brown + black + green/yellow (3x)
Characteristics
Construction characteristics | |
---|---|
Conductor material | Bare copper |
Conductor flexibility | Flexible class 5 |
Insulation | XLPE (Cross-linked Polyethylene) |
Core identification | Brown, black, grey, green / yellow |
Screen | Aluminium tape + tinned copper braid |
Outer sheath | HFFR (Halogene Free Flame Retardant) |
Sheath colour | Black |
Construction type | 4 x 1.5 |
Lead free | Yes |
Dimensional characteristics | |
Copper content | 95kg/km |
Nominal outer diameter | 11.0mm |
Approximate weight | 230kg/km |
Electrical characteristics | |
Permissible current rating in open air | 23A |
Max. continuous operating voltage Uc | 1.2kV |
max.peak voltage (num) | 1.7kV |
Test voltage | 4000V |
Rated Voltage Uo/U (Um) | 0.6/1 kV |
Mechanical characteristics | |
Cable flexibility | Semi-flexible |
Mechanical resistance to impacts | Normal industrial use |
Usage characteristics | |
Electro magnetic interference resistance | Yes |
U.V resistance | Yes |
Ambient dynamic operating temperature, range | -5 .. 90°C |
Ambient static operating temperature, range | -20 .. 90°C |
Dynamic bending factor | 20(xD) |
Bending factor when installed | 10(xD) |
Max. conductor temperature in service | 90°C |
RoHS compliant | Yes |
Oil resistance | Yes |
Ozone resistance | Yes |
Docs and info
Electrical Datas
Type |
Capacitance |
Inductance |
Reactance |
AC Resistance |
Voltage drop |
|
nF/km |
mH/km |
Ω [50Hz] |
Ω/km [90°C] |
mV/A*m [90°C] |
4 x 1,5 |
203 |
0.311 |
0.0977 |
16.931 |
30.476 |
4 x 2,5 |
256 |
0.290 |
0.0910 |
10.159 |
18.285 |
4 x 4 |
280 |
0.272 |
0.0853 |
6.301 |
11.342 |
4 x 6 |
329 |
0.259 |
0.0812 |
4.201 |
7.562 |
4 x 10 |
394 |
0.244 |
0.0765 |
2.431 |
4.377 |
3x16 + 3x2,5 |
260 |
0.233 |
0.0733 |
1.540 |
2.773 |
3x25 + 3x4 |
268 |
0.234 |
0.0736 |
0.993 |
1.787 |
3x35 + 3x6 |
300 |
0.228 |
0.0718 |
0.705 |
1.269 |
3x50 + 3x10 |
311 |
0.226 |
0.0710 |
0.491 |
0.884 |
3x70 + 3x10 |
343 |
0.224 |
0.0703 |
0.346 |
0.623 |
3x95 + 3x16 |
369 |
0.219 |
0.0689 |
0.262 |
0.472 |
3x120 + 3x16 |
401 |
0.218 |
0.0686 |
0.205 |
0.369 |
3x150 + 3x25 |
407 |
0.220 |
0.0690 |
0.164 |
0.296 |
3x185 + 3x35 |
411 |
0.221 |
0.0693 |
0.135 |
0.243 |
3x240 + 3x50 |
418 |
0.219 |
0.0687 |
0.102 |
0.184 |
Selling information
Marking
- Nexans Rheyflex® Power EMC HFFR 2XSLSTCH-J N° of cores x cross-section 0,6/1 kV CE,
- Sample 1: Nexans Rheyflex® Power EMC HFFR 2XSLSTCH-J 3x240 + 3x50 0,6/1 kV CE
- Sample 2: Nexans Rheyflex® Power EMC HFFR 2XSLSTCH-J 4x6 0,6/1 kV CE