Description
- Individual & Overall Screen (IOS)
- Oil resistant
Standards
International : IEC 60331; IEC 60332-3-22 Cat.ADescription
Applications
These instrumentation and communication cable are used to transmit analogue or digital signals in measurement and process control where chemicals may be present. The individual screening of each pair limits the consequence of crosstalk. They maintain circuit integrity when exposed to fire.
Design
Conductor:
Stranded bare copper class 2
Insulation:
Mica tape
Cross-linked polyethylene (XLPE)
Individual screen:
Polyester tape
Tinned copper drain wire
Aluminium backed polyester tape
Polyester tape
Overall screen:
Polyester tape
Tinned copper drain wire
Copper backed polyester tape
Outer sheath:
Polyvinyl chloride (PVC)
Colour: black
Other colour on request.
Core identification
Pair: white - black
White core printed with pair number
Marking
NEXANS 279 MGT/XLPE/IND.+OA.SCR/PVC 170/300V Nber of pairs & cross-section Cu IEC 60331 IEC 60332-3-22(A) MM YYYY Manufacturing number + metric marking
Standards
EN 50288-7 (Design guide-lines)
Characteristics
Construction characteristics | |
---|---|
Conductor material | Bare copper |
Type of conductor | Stranded, Class 2 |
Insulation | Micatape + XLPE |
Individual screen | Tinned copper drain wire + aluminium/polyester tape |
Overall screen | Tinned copper drain wire + copper polyester tape |
Outer sheath | PVC |
Protection | no |
Dimensional characteristics | |
Number of pairs | 5 |
Conductor cross-section | 1.5mm² |
Conductor diameter | 1.5mm |
Diameter over insulation | 3.24mm |
Minimum outer diameter | 20.1mm |
Maximum outer diameter | 22.1mm |
Approximate weight | 460kg/km |
Electrical characteristics | |
Rated Voltage Uo/U (Um) | 170/300V |
Usage characteristics | |
Fire resistant | IEC 60331 |
Fire retardant | IEC 60332-3-22 |
Oil resistance | Yes |
Electro magnetic interference resistance | Yes |
Operating temperature, range | -20 .. 60°C |
Max. conductor temperature in service | 90°C |
Standard | EN |
Docs and info
Selling information
Other fire performances IEC 60332-1 or IEC 60332-3-24(C) and enhanced hydrocarbon resistance on request.
Minimum bending radius:
10 x outer diameter
To be doubled during laying operations
Tinned copper conductors available on request