Description
- Armoured (Type 2)
- Individual & Overall Screen (IOS)
- Oil resistant
Standards
International : IEC 60331; IEC 60332-3-22 Cat.ADescription
Applications
These Instrumentation and communication are used to transmit analogue or digital signals in measurement and process control. They are well adapted to underground use in industrial applications where chemical and mechanical protections are needed (refinery areas, chemical plant...). The individual screening of each pair limits the consequence of crosstalk. They maintain circuit integrity when exposed to fire.
Design
Conductor:
Stranded or flexible bare copper
Insulation:
Mica tape
Cross-linked polyethylene (XLPE)
Individual screen:
Binder tape
Tinned copper drain wire
Aluminium/polyester tape
Binder tape
Overall screen:
Binder tape
Tinned copper drain wire
Aluminium/polyester tape
Bedding (inner sheath):
Low Smoke Zero Halogen (LSZH)
Armour:
Galvanized steel wires (SWA)
Outer sheath:
Polyvinyl chloride (PVC)
Colour: black
Other colour on request.
Core identification
Pair: black - white
White core printed with pair number
On request according to PAS 5308 part 1
Marking
NEXANS 279 MGT/XLPE/IND.+OA.SCR/LSZH/SWA/PVC 300/500V Nber of pairs & cross-section Cu IEC 60331 IEC 60332-3-22(A) MM YYYY Manufacturing number + metric marking
Standards
PAS 5308 Part 1/type 2 (Design guide-lines)
BS EN 60228-2005
Characteristics
Construction characteristics | |
---|---|
Conductor material | Bare copper |
Type of conductor | Stranded, Class 2 |
Insulation | Micatape + XLPE |
Individual screen | Tinned copper drain wire + aluminium/polyester tape |
Overall screen | Tinned copper drain wire + aluminium/polyester tape |
Inner sheath | Low smoke, zero halogen thermoplastic compound |
Armour type | Galvanized steel wires |
Outer sheath | PVC |
Protection | Yes |
Dimensional characteristics | |
Number of pairs | 2 |
Conductor cross-section | 1mm² |
Conductor diameter | 1.28mm |
Diameter over insulation | 2.8mm |
Diameter over inner sheath | 12.8mm |
Diameter over armour | 14.6mm |
Minimum outer diameter | 17.1mm |
Maximum outer diameter | 18.8mm |
Approximate weight | 487kg/km |
Electrical characteristics | |
Rated Voltage Uo/U (Um) | 300 / 500 V |
Mechanical characteristics | |
Mechanical resistance to impacts | Good |
Usage characteristics | |
Fire resistant | IEC 60331 |
Fire retardant | IEC 60332-3-22 |
Oil resistance | Yes |
Electro magnetic interference resistance | Yes |
Operating temperature, range | -20 .. 60°C |
Max. conductor temperature in service | 90°C |
Standard | PAS |
Docs and info
Selling information
Other fire performances IEC 60332-1 or IEC 60332-3-24(C) and enhanced hydrocarbon resistance on request.
Minimum bending radius:
10 x outer diameter
To be doubled during laying operations
Tinned copper conductors available on request