Description
- Overall Screen (OS)
- Hydrocarbons resistant and enhanced resistance to aromatics
Standards
International : IEC 60332-1-2National : NF C 32-070/C2
Description
Applications
These instrumentation and communication cables are used to transmit analogue or digital signals in measurement and process control. They are well adapted to underground use in industrial applications, in moist areas, where hydrocarbon and mechanical protection are needed. The lead cover brings an enhanced resistance to aromatics hydrocarbons.
Nexans code
- 1st serie = number of pairs, triples or quads: 01 to 27
- 2nd serie = pair (IP), triple (IT), quad (IQ)
- 3rd serie = conductor 05 (1 x 0.8 mm), 09 (7 x 0.4 mm) or 15 (7 x 0.52 mm)
- 4th serie = overall screen (EG), individual screen + overall screen (EI)
- 5th serie = mechanical protection: without metal tape (SF), with steel tape (FA), with lead and steel tape (PF)
Design
Conductor:
- Solid plain copper 0.50 mm² (1 x 0.80 mm) or stranded plain copper cross-section 0.88 mm² (7 x 0.40 mm) or 1.5 mm² (7 x 0.52 mm)
Insulation:
- Polyvinyl chloride (PVC)
Overall screen:
- Polyester tape
- Tinned copper drain wire
- Aluminium/polyester tape
Inner sheath:
- Polyvinyl chloride (PVC)
Lead covering
Armour:
- Paraffin-waxed crepe paper
- Double steel tape
Outer sheath:
- Polyvinyl chloride (PVC)
- Colour: light-blue or grey
Core identification
Pair: natural - red
Triple: natural - red - blue
Quad: natural - red - blue - yellow
Natural cores printed with pair/triple number
Marking
NEXANS 279 - Number of pair/triple/quad IP/IT/IQ 05/09 EG PF + metric marking
Characteristics
Construction characteristics | |
---|---|
Conductor material | Plain copper |
Insulation | PVC |
Overall screen | Tinned copper drain wire + aluminium/polyester tape |
Inner sheath | PVC |
Lead Sheath | Yes |
Armour type | Steel tapes |
Outer sheath | PVC |
Sheath colour | Grey |
Dimensional characteristics | |
Conductor cross-section | 0.88mm² |
Number of pairs | 0 |
Number of triples | 7 |
Number of quads | 0 |
Lead cover diameter | 19.4mm |
Diameter over armour | 21.2mm |
Minimum outer diameter | 23.1mm |
Maximum outer diameter | 25.5mm |
Approximate weight | 1397kg/km |
Electrical characteristics | |
Operating voltage | 250V |
Mechanical characteristics | |
Mechanical resistance to impacts | Good |
Usage characteristics | |
Flame retardant | NFC 32070 C2, IEC 60332-1-2 |
Chemical resistance | Hydrocarbons resistant and enhanced resistances to aromatics |
Electro magnetic interference resistance | Yes |
Operating temperature, range | -20 .. 60°C |
Max. conductor temperature in service | 70°C |
Standard | NFM |
Docs and info
Selling information
Minimum bending radius:
10 x outer diameter
To be doubled during laying operations