Description
- XLPE insulation
- Overall Screen (OS)
- With lead cover
- Aliphatic and aromatic hydrocarbons resistant
Standards
International : IEC 60332-3-22 Cat.ADescription
Applications
These cables are used for telecommunication and DCS Data highway for OSP telephone communication and Public Address System. They are well adapted to underground use in industrial applications, in moist areas, where hydrocarbon and mechanical protections are needed. The lead cover brings an enhanced resistance to aromatics hydrocarbons.
Design
Conductor:
Solid, bare copper
Insulation:
Cross-linked polyethylene (XLPE)
Overall screen:
Binder tape
Tinned copper drain wire
Aluminium/polyester tape
Bedding (inner sheath):
Polyvinyl chloride (PVC)
Colour: black
Lead covering:
Bedding (intermediate sheath):
Polyvinyl chloride (PVC)
Colour: black
Armour:
Galvanized steel wires (SWA)
Outer sheath:
Polyvinyl chloride (PVC)
Colour: black
Other colour on request.
Core identification
Pair: black - white
Quad: black - white - red - blue (2 pair cables assembled as a quad)
White core printed with pair number
Marking
NEXANS 279 XLPE/OA.SCR/PVC//LC/PVC/SWA/PVC 110 V Nber of pairs & cross-section Cu IEC 60332-3-22(A) MM YYYY Manufacturing number + metric marking
Characteristics
Construction characteristics | |
---|---|
Conductor material | Bare copper |
Insulation | XLPE (Cross-linked Polyethylene) |
Overall screen | Tinned copper drain wire + aluminium/polyester tape |
Inner sheath | PVC |
Lead Sheath | Yes |
Intermediate sheath | PVC |
Armour type | Galvanized steel wires |
Outer sheath | PVC |
Protection | Yes |
Dimensional characteristics | |
Conductor cross-section | 1.5mm² |
Number of pairs | 19 |
Conductor diameter | 1.39mm |
Diameter over insulation | 2.59mm |
Diameter over inner sheath | 27.9mm |
Diameter over lead sheath | 30.9mm |
Diameter over intermediate sheath | 33.3mm |
Diameter over armour | 38.3mm |
Minimum outer diameter | 40.3mm |
Maximum outer diameter | 44.4mm |
Approximate weight | 4256kg/km |
Electrical characteristics | |
Operating voltage | 110V |
Mechanical characteristics | |
Mechanical resistance to impacts | Good |
Usage characteristics | |
Fire retardant | IEC 60332-3-22 |
Chemical resistance | Aliphatic and aromatic hydrocarbons resistant |
Electro magnetic interference resistance | Yes |
Operating temperature, range | -20 .. 60°C |
Max. conductor temperature in service | 90°C |
Docs and info
-
Electrical characteristics
Electrical loop
resist.at 20 Cmax. (Ohms/km)
Loop Inductance
(mH/km)
Capacitance max.
(nF/km)
L / R ratio max
(µH/Ohms)
4x2x1 36.9 0.697 115 25 5x2x1 36.9 0.697 115 25 10x2x1 36.9 0.697 115 25 25x2x1 36.9 0.697 115 25 50x2x1 36.9 0.697 115 25 100x2x1 36.9 0.697 115 25 2x2x1,5 24.6 0.656 115 40 3x2x1,5 24.6 0.656 115 40 19x2x1,5 24.6 0.656 115 40
Selling information
Other fire performances IEC 60332-1 or IEC 60332-3-24(C) on request.
Minimum bending radius:
10 x outer diameter
To be doubled during laying operations