Description
Standards
International : IEC 60092;IEC 60331;IEC 60332-1;IEC 60332-3;IEEE 383;LLOYDS Reg. 91/00126(E1);UIC 895;VERITAS N°09555/A0 BV ACE1/723 PC 2502HNational : BSS 6195-T5-C-D-E-F;DIN VDE 0472;NF F 16-101/BF1
Description
SIWO-KUL® S10 cables are required when high flexibility and high temperature conditions are present; they are mainly used for connecting MV Drives to motors.
SIWO-KUL® S10 12 kV cables are specifically engineered for use in variable frequency AC motor drive (VFD) applications.
Construction
- Copper conductor tinned, flexible IEC 60228, class 5
- Tape (up 16 mm²)
- Semi-conductive layer (only for 6.6 and 12 kV)
- Silicone rubber insulation
- Semi-conductive layer (only for 6.6 and 12 kV)
- Tinned copper braid
- Separator tape
- Protective synthetic yarn braiding, PUR varnished
The use of silicone rubber, a high grade corona resistant insulation material, gives the cable excellent dielectric strength.
The braided synthetic yarn covering, which is applied directly over the insulation, gives the cable, because of its short braiding pitch and high compactness, an excellent mechanical protection by maintaining good flexibility.
Operating temperature for continuous service extends from –55°C up to 180°C.
These products are also part of our Windlink® offer for Wind turbines.
Approvals
These cables are UL (Underwriters Laboratories inc.) approved for Appliance Wiring Material (AWM), following styles 3640, 3641, 3642 and 3643, CSA File No.: 036040-0-000.
SIWO-KUL® S10 cables are in compliance with EU directive on the limits of certain metals and waste as defined on ROHS (Restriction of Hazardous Substances) and WEE (Waste from Electrical and Electronic Equipment).
SIWO-KUL® S10 is REACH conform (no substances benzene, C10-C13).
Characteristics
Construction characteristics | |
---|---|
Conductor material | Tinned copper |
Conductor flexibility | Flexible class 5 |
Insulation | Special Silicone |
Halogen free | Yes |
Outer sheath | Synthetic yarn braiding |
Construction type | 328 x 0.50 |
Dimensional characteristics | |
Conductor cross-section | 70mm² |
Nominal outer diameter | 24.4mm |
Approximate weight | 1122kg/km |
Conductor diameter | 11.85mm |
Precision of diameter | +/- 0.3 mm |
Electrical characteristics | |
Operating voltage | 12kV |
Maximum peak voltage | 0. .. 20.kV |
Test voltage | 31kV |
Max. DC resistance of the conductor at 20°C | 0.277Ohm/km |
Breakdown voltage | 50kV |
Breakdown field strength (kV/mm) | > 20 |
Loss factor tan d | < 10-2 |
Dielectric constant ER | 3 .. 4 |
Mechanical characteristics | |
Minimum Tensile Strength | 8.0MPa |
Cable flexibility | Flexible |
Elongation at break of insulation (%) | > 250 |
Hardness of insulation (Shore A) | 65.0 .. 70.0 |
Usage characteristics | |
Minimum static operating bending radius | 147.3mm |
Operating temperature, range | -55 .. 180°C |
Chemical resistance | Good |
Oil resistance | Yes |
Flame retardant | IEC 60332-1 |
Fire retardant | IEC 60332-3 |
Fire resistant | IEC 60331 |
Gases corrosivity | IEC 60754-1, IEC 60754-2 |
Smoke density | IEC 61034 |
Packaging | Cut to length |
Docs and info
-
Permissible continuous current carrying capacity 12 kV
Cables separated: 1D
The values determined from the diagram are based on the following assumptions:
a) Cables separated.
Space between adjacent cables ≥ 1 x d.
b) Conductor temperature = See tables below
c) Without additional cooling.
Suffcient natural air fow ensured.
Selling information
Marking
Our SIWO-KUL® S cables have been printed:
NEXANS SWITZERLAND SIWO-KUL® S + voltage in kV + section in mm² + Standards + Meter marks