Case study

Resisting heavy ice loads in the Carpathian mountains with Nexans LoSag conductors

  • STANDORT
    Romania
  • PARTNERSCHAFT
    Transelectrica
  • Market
    Overhead Lines

Optimize capital expenditure without compromising performance

Transelectrica, the Romanian TSO, needed to upgrade its Stejaru – Fantanele – Gheorgheni 220kV line, representing a total of 448 km of conductors. The objective was to double ampacity while keeping existing clearances

The line route crosses several topologies of specific climatic constraints. Especially, one section passes over mountain peaks and is exposed to heavy ice load conditions

ACSS in valleys, HTLS LoSag in mountains

Nexans proposed and supplied a reconductoring solution including 2 conductor designs. This allowed to optimize project CAPEX by adapting the mechanical performance of the conductor to the topological and climatic constraints of the each section :

  • ACSS 423-AL0/58-5MS8A conductor for sections located in lowland areas (354 km)
  • ACPR LoSag 408-AT1/57 conductor for sections at higher altitude (94 km) and subjected to heavy ice load conditions.
94 km

of Nexans ACPR LoSag conductors installed

1320 Amps

Line Ampacity at 150°C

160 GPa

Composite Core Modulus

2024

Installation year

Nexans solution

LoSag conductors were first commercialized by Nexans in 2011. They feature a composite core exclusively  made of long carbon fibers. This lightweight strengthening element provides high modulus and breaking load compared to standard solutions. When combined with thermal aluminum wires, LoSag conductors allow to double line ampacity while respecting existing clearances even in case of ice accretion on the conductor.

For this project, Nexans ACPR LoSag 408-AT1/57 was selected by Nexans OHL technical experts as a result of a thorough sag tension study.

The conductor was installed in 2024 as a single bundle.

Main features:

  • Conductor diameter: 25.4 mm
  • Linear weight: 1.26 kg/m
  • Breaking Load: >14.7 mtons
  • Elasticity modulus above knee point: 160 GPa
  • Design Ampacity: 1320A at 150°C
  • Maximum continous operating temperature: 150°C by design
  • Line Voltage: 220kV
Contact
Let's start your project together

Tell us about your project details, we will prepare the best conductor design

Contact us now

Kontaktieren Sie uns

Themen zu denen Sie weitere Informationen wünschen:

benötigte Felder*

Bitte überprüfen Sie Ihre Eingabe und versuchen Sie es erneut.

Eine Email Adresse muss ein einzelnes @ enthalten

Schutz personenbezogener Daten

Sie haben das Recht, der Verarbeitung Ihrer personenbezogenen Daten und / oder deren Verwendung für Direktmarketing- oder kommerzielle Zwecke zu widersprechen

Vielen Dank!

Danke, dass sie uns kontaktiert haben. Wir werden uns in Kürze mit Ihnen in Verbindung setzen.

Fehler

Ein Fehler ist aufgetreten. Bitte versuchen Sie es erneut.

Schliessen